在GB50974《消防給(gei)水及(ji)消火栓(shuan)系(xi)(xi)統(tong)技術規范(fan)》埋地管(guan)道,當(dang)(dang)系(xi)(xi)統(tong)工(gong)作壓(ya)力(li)(li)不大(da)(da)于(yu)(yu)(yu)1.20MPa時,宜(yi)(yi)采(cai)用球(qiu)墨鑄鐵(tie)管(guan)或(huo)鋼絲網骨架塑料(liao)復合管(guan)給(gei)水管(guan)道;當(dang)(dang)系(xi)(xi)統(tong)工(gong)作壓(ya)力(li)(li)大(da)(da)于(yu)(yu)(yu)1.20MPa小(xiao)于(yu)(yu)(yu)1.60MPa時,宜(yi)(yi)采(cai)用鋼絲網骨架塑料(liao)復合管(guan)、加厚(hou)鋼管(guan)和無(wu)(wu)縫(feng)鋼管(guan);當(dang)(dang)系(xi)(xi)統(tong)工(gong)作壓(ya)力(li)(li)大(da)(da)于(yu)(yu)(yu)1.60MPa時,宜(yi)(yi)采(cai)用無(wu)(wu)縫(feng)鋼管(guan)。鋼管(guan)連(lian)(lian)接(jie)宜(yi)(yi)采(cai)用溝槽(cao)連(lian)(lian)接(jie)件(jian)(卡箍)和法蘭,當(dang)(dang)采(cai)用溝槽(cao)連(lian)(lian)接(jie)件(jian)連(lian)(lian)接(jie)時,公稱直(zhi)徑小(xiao)于(yu)(yu)(yu)等(deng)于(yu)(yu)(yu)DN250的溝槽(cao)式(shi)管(guan)接(jie)頭系(xi)(xi)統(tong)工(gong)作壓(ya)力(li)(li)不應大(da)(da)于(yu)(yu)(yu)2.50MPa,公稱直(zhi)徑大(da)(da)于(yu)(yu)(yu)等(deng)于(yu)(yu)(yu)DN300的溝槽(cao)式(shi)管(guan)接(jie)頭系(xi)(xi)統(tong)工(gong)作壓(ya)力(li)(li)不應大(da)(da)于(yu)(yu)(yu)1.60MPa。


  常用(yong)地下管道材料(liao)見表4-21


21.jpg


 

  這(zhe)些材料選用的(de)(de)設(she)計要求,也影響裝置(zhi)、罐區的(de)(de)布(bu)置(zhi)。