(1)隔熱(re)厚度的(de)計算、保溫和人(ren)身防(fang)護,采(cai)用(yong)介質(zhi)正(zheng)常操作溫度,保冷及防(fang)結露(lu),采(cai)用(yong)最小(xiao)操作流體(ti)溫度。
(2)保(bao)(bao)溫(wen)(wen)厚(hou)度(du)的計算,當無(wu)特(te)殊工(gong)藝要求時,采用(yong)“經濟厚(hou)度(du)”法計算,人身防護保(bao)(bao)溫(wen)(wen)厚(hou)度(du)按“表面溫(wen)(wen)度(du)法”計算,但(dan)保(bao)(bao)溫(wen)(wen)層外表面的溫(wen)(wen)度(du)不(bu)得大于60℃。
(3)保(bao)冷(leng)(leng)層(ceng)(ceng)厚(hou)度(du)(du)的(de)計(ji)算(suan)原則(ze):①. 為減(jian)少(shao)冷(leng)(leng)量(liang)損失的(de)保(bao)冷(leng)(leng)層(ceng)(ceng),應(ying)(ying)采(cai)用“經濟厚(hou)度(du)(du)法(fa)”計(ji)算(suan)厚(hou)度(du)(du)。②. 為防止外(wai)表(biao)(biao)面(mian)結露的(de)保(bao)冷(leng)(leng)層(ceng)(ceng)應(ying)(ying)采(cai)用“表(biao)(biao)面(mian)溫度(du)(du)法(fa)”計(ji)算(suan)厚(hou)度(du)(du)。③. 工藝上(shang)允許一定量(liang)冷(leng)(leng)損失的(de)保(bao)冷(leng)(leng)層(ceng)(ceng),應(ying)(ying)用“熱平衡法(fa)”計(ji)算(suan)厚(hou)度(du)(du)。外(wai)表(biao)(biao)的(de)溫度(du)(du)應(ying)(ying)高于露點溫度(du)(du)1~3℃。
(4)對設備和管道的(de)管口和其他突(tu)起部(bu)分(包(bao)括(kuo)鋼結構部(bu)件),隔熱(re)(re)厚度一(yi)般將(jiang)根(gen)據上述同樣方法決定。塔(ta)的(de)內部(bu)溫度隨高度而(er)變化,絕熱(re)(re)厚度也(ye)相應變化。
(5)絕熱層厚(hou)度(du)應(ying)以10mm為單位進行分檔。硬質泡沫塑料最(zui)小(xiao)厚(hou)度(du)可為20mm,其他(ta)硬質絕熱材料制品最(zui)小(xiao)厚(hou)度(du)可為30mm。
圓筒形設備和管(guan)道的公(gong)稱直(zhi)徑(jing)大于1m時,應(ying)按平面計(ji)算(suan)絕(jue)(jue)熱(re)(re)層(ceng)厚度;公(gong)稱直(zhi)徑(jing)小于或等(deng)于1m時,應(ying)按圓筒計(ji)算(suan)絕(jue)(jue)熱(re)(re)層(ceng)厚度。
絕(jue)(jue)熱層(ceng)(ceng)(ceng)(ceng)(ceng)厚(hou)度大(da)于(yu)80mm時,應分兩層(ceng)(ceng)(ceng)(ceng)(ceng)或多(duo)層(ceng)(ceng)(ceng)(ceng)(ceng)施(shi)工。當內外(wai)層(ceng)(ceng)(ceng)(ceng)(ceng)采用同種絕(jue)(jue)熱材(cai)(cai)料時,內外(wai)層(ceng)(ceng)(ceng)(ceng)(ceng)厚(hou)度宜(yi)近似相等。當內外(wai)層(ceng)(ceng)(ceng)(ceng)(ceng)為不(bu)(bu)同絕(jue)(jue)熱材(cai)(cai)料時,內外(wai)層(ceng)(ceng)(ceng)(ceng)(ceng)厚(hou)度的比例應保證(zheng)內外(wai)層(ceng)(ceng)(ceng)(ceng)(ceng)界面處溫(wen)度絕(jue)(jue)對(dui)值(zhi)不(bu)(bu)超過外(wai)層(ceng)(ceng)(ceng)(ceng)(ceng)材(cai)(cai)料推薦使用溫(wen)度絕(jue)(jue)對(dui)值(zhi)的0.9倍;對(dui)于(yu)保冷設計,應取保冷材(cai)(cai)料推薦使用溫(wen)度(T2)下限值(zhi)的0.9倍。
(6)SH/T 3010《石油化工(gong)設(she)備(bei)(bei)和管道(dao)絕熱工(gong)程(cheng)設(she)計(ji)規范》、GB50264《工(gong)業設(she)備(bei)(bei)及管道(dao)絕熱工(gong)程(cheng)設(she)計(ji)規范》、GB/T8175《設(she)備(bei)(bei)及管道(dao)絕熱設(she)計(ji)導則(ze)》、GB/T 4272《設(she)備(bei)(bei)及管道(dao)絕熱技術通則(ze)》等規范的(de)隔(ge)熱厚度計(ji)算(suan)方法基(ji)本一致,介紹得非常詳細,所以在此就不過(guo)多地(di)闡(chan)述。