①. NFPA 30在(zai)對地(di)上儲罐的(de)布置規定(ding)(ding)時(shi),提到了不(bu)穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)(unstable liquid)和穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)(stable liquid)的(de)概念。不(bu)穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)是指在(zai)純(chun)凈狀態或在(zai)商(shang)業生(sheng)(sheng)產(chan)、運輸過程中(zhong),承受震動、壓力(li)或溫(wen)度(du)條件下,可(ke)能產(chan)生(sheng)(sheng)劇烈的(de)聚合(he)、分(fen)(fen)解、縮合(he)反應(ying)和自反應(ying)現(xian)象(xiang)的(de)液(ye)體(ti)(ti)(ti),而任何沒有被定(ding)(ding)義為“不(bu)穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)”的(de)液(ye)體(ti)(ti)(ti)即為穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)。如此(ci),煉廠所涉及大部分(fen)(fen)原(yuan)料、中(zhong)間(jian)(jian)料及產(chan)品(pin),如原(yuan)油、汽油組(zu)分(fen)(fen)及產(chan)品(pin)、柴油組(zu)分(fen)(fen)及產(chan)品(pin)、煤油組(zu)分(fen)(fen)及產(chan)品(pin)等均(jun)屬(shu)于穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)。對儲存穩(wen)(wen)定(ding)(ding)液(ye)體(ti)(ti)(ti)的(de)地(di)上儲罐罐壁(bi)對罐壁(bi)的(de)最小間(jian)(jian)距要(yao)求見表2.5。
表2.5 NFPA 30 對儲存穩定液體的(de)地上儲罐罐壁對罐壁的(de)最(zui)小間距要求

注:容量不超過480m3的原油罐,且位于孤立地區的采油設施附近,間隔可以不需要大于0.9m。
②. 僅儲存ⅢB級液體的儲罐(guan)且不在儲存I級或(huo)II級液體儲罐(guan)的防(fang)火堤或(huo)排液通道的區(qu)域(yu)內,其(qi)間距最小為0.9m。如果(guo)儲存在同(tong)一防(fang)火堤或(huo)排液通道的區(qu)域(yu)內,應按(an)上表IIIA級液體考慮間距。
③. 對于不穩定液體的儲罐和其他儲存不穩定液體或儲存Ⅰ級、Ⅱ級、Ⅲ級穩定液體的儲灌最小間距不應小于其直徑和的一半。
④. 國內(nei)GB 50160強調罐組的概念,對一個(ge)罐組內(nei)的總容積(ji)及儲罐總個(ge)數均有明確要求,NFPA 30 沒有強調。
⑤. 關于相鄰儲(chu)罐的安(an)全間(jian)距,兩者均同時從儲(chu)罐直徑(或直徑與高(gao)度的較(jiao)大值)、儲(chu)罐型式及儲(chu)存類別(bie)的角度出(chu)發,具體規定各劃(hua)分區域內(nei)安(an)全間(jian)距。
工程(cheng)應用:按NFPA 30 儲罐間距(ju)設計實例
某項目原油(甲B)罐組,共4座50000m3浮頂儲罐(直徑×高度=55m×20m),另(ling)有一(yi)個中間罐組,共設有4座丙A(ⅢA)級5000m3拱頂儲罐(直徑×高度=20m×16m)。依據NFPA 30設計儲罐間距,見表2.6。